Simple. Trusted. Compliance.Directly employed engineers · Nationwide coverageRG Connect customer login ↗
Electrical testing · Question explained

What changed in EICR reporting under Amendment 4:2026?

Amendment 4 changed how FI relates to the overall EICR outcome. That matters if your property team uses a spreadsheet, a CAFM rule or an internal checklist to decide which electrical findings need attention.

Request an EICR quote
The short answer

Does an FI observation still automatically make an EICR unsatisfactory?

Not under BS 7671:2018+A4:2026. The IET explains that FI and C3 are separate from the C1/C2 classifications that determine an unsatisfactory outcome. FI advises investigation. Read the report’s declared edition, its recipient notes and the inspector’s written observation before deciding what action is needed.

The practical task is to understand the report you have, preserve its history and agree a response to the actual observation. This article explains the current change and sets out a document-review process for commercial premises. It does not reclassify an existing inspection or diagnose an installation.

In this article 6 sections
  1. Start with the edition recorded on the report
  2. An advisory observation still needs a decision
  3. Keep historic reports intact
  4. Review the rules in your property systems
  5. Brief a contractor on the work you actually need
  6. A short checklist for the report owner
01

Start with the edition recorded on the report

Amendment 4 was published in April 2026. The IET’s edition checker says the previous transition ended on 15 October 2026 and identifies A4 as the current edition. Its July explanation describes the changed treatment of FI. Those two sources answer different questions: which edition is current, and what changed in the reporting approach.

For a property record, retain the complete report rather than extracting only its front-page outcome. Check the stated standard or amendment, inspection date, observations and guidance for the recipient. If the edition is missing or the form is unclear, ask the issuing organisation to explain it. Do not infer the edition from a filename, upload date or the colour of a downloaded document.

02

An advisory observation still needs a decision

The current distinction should help a reader separate findings that determine an unsatisfactory outcome from advisory observations. It does not turn the observation list into a set of items that can be ignored whenever the overall result is satisfactory.

Ask what the FI observation refers to, which part of the installation is affected and what information or investigation would resolve it. A useful response records an owner, the agreed action and a review date. The competent inspector’s explanation should guide that response; a software colour or an automatically assigned task title should not replace it.

  • Keep the full written observation and its location reference.
  • Ask what remains uncertain and what work would establish the position.
  • Record any operating restrictions or immediate measures communicated separately.
  • Retain the resulting investigation records with the original EICR.
03

Keep historic reports intact

Suppose a managing agent holds an earlier report and is preparing a new inspection tender. The record should continue to show what the earlier inspector issued. Replacing its outcome in a portfolio spreadsheet without explanation can make it difficult to understand why work was authorised or which evidence closed an action.

A clearer approach is to preserve the original PDF and add a dated management note explaining any later advice, investigation or remedial evidence. A new report belongs in the record as a new assessment. It should not silently overwrite the earlier file simply because both concern the same property.

This is an illustrative records-management example, not a Reaction customer case study. The appropriate interpretation of any particular report needs to be confirmed with a competent person who can review the document and circumstances.

04

Review the rules in your property systems

A portfolio workflow may contain more assumptions than the visible report. Check spreadsheet formulas, mandatory form fields, help text and task-routing rules. If a rule treats every FI entry as equivalent to C1 or C2, establish which reporting editions that rule was designed for before changing it.

Keep the outcome field separate from the action register. One describes the issued assessment; the other manages follow-up. Combining them into one red or green cell can lose useful information about advisory work, incomplete investigation or an action that has not yet been reviewed.

RecordUseful information to preserve
Issued reportReference, date, declared edition and original overall outcome
ObservationExact finding, classification and installation reference
Management actionOwner, agreed response, deadline and any authorisation
Follow-up evidenceInvestigation or work record, review decision and date
05

Brief a contractor on the work you actually need

A request that says only “make the EICR satisfactory” may leave important questions unanswered. Provide the complete report and identify whether you want a new periodic inspection, investigation of a particular observation or a quotation for defined remedial work. These are different scopes and may require different site arrangements.

Explain access to the affected boards or circuits, who can authorise isolation and what records the organisation expects afterwards. If the scope is still uncertain, say so. Asking for clarification is more useful than supplying a guessed repair quantity or assuming that an inspection price includes every resulting action.

06

A short checklist for the report owner

Before closing the review, make sure someone can explain both the issued outcome and the status of each action. That gives the next property manager a usable record and makes the next inspection conversation more precise.

Standards guidance and reporting forms can change. Use the current IET edition information when setting a new specification, and keep the edition attached to historic records. An electrical installation’s actual condition and any communicated danger still require a competent response; this article is a reading and planning aid.

Practical checklist
  • Complete report and recipient notes retained
  • Edition and inspection date identified
  • Unclear observations discussed with the issuer
  • Operating advice and immediate measures recorded
  • Investigation or remedial scope separately defined
  • Owner and evidence review date assigned
Related questions

EICR testing questions.

Should I change the outcome on an older EICR?

Do not rewrite an issued report yourself. Retain the original and ask a competent reviewer or its issuer to explain how its edition and observations should be interpreted. Record later advice and work as dated follow-up evidence.

Does a satisfactory outcome mean no work is needed?

Read the complete observations and recipient guidance. An overall outcome does not replace a maintenance decision about advisory findings or an agreed investigation.

Should I order another EICR to resolve an FI?

Not automatically. Share the existing report and ask whether the required scope is investigation, remedial work or a new inspection. Confirm access and the records required before commissioning it.

Research & further reading

Sources used for this article.

The linked guidance supports the factual context. Check its jurisdiction and the requirements for your actual premises.

  1. IET: Further investigation and Amendment 4 reporting ↗

    Explains the changed relationship between FI, C3 and the overall EICR outcome.

  2. IET: Current edition and transition information ↗

    Confirms the current amendment and the end of the previous transition.

Inspection service

EICR testing: scope & records.

See what the service includes and which site details help prepare a relevant quote.

View the service details
Quote enquiry

Request an EICR quote

Choose whether you need a new inspection, a discussion about findings or work across several sites.

No contact details needed for these first questions.Prefer to talk? 0203 885 2299
Call the teamGet a quote