How should a business prepare an equipment inventory for PAT?
List the equipment by location and use, give each item a stable identifier and include its mains leads, chargers and relevant accessories. Record ownership, availability and known defects. Agree how detachable components are counted and reported, then keep missing, failed and retired items distinct from equipment actually inspected or tested.
The most valuable question before an equipment visit is often what should be here.
Without an inventory, a contractor can record everything presented and still miss the tools in vans, the spare chargers in drawers and the equipment on another shift. A useful register gives the business a way to reconcile those gaps. It also prevents a misleading total from becoming the main measure of success. The purpose is to know what equipment exists, which maintenance actions apply and what remains outstanding. This guide explains how to build that register without turning it into an unmanageable database.
In this guide 5 sections
Read the guide offline or copy its planning points into your own records.
Download this guide as textStart with locations and work activities
Divide the site into areas that people can actually find: named rooms, numbered workstations, workshops, stores and mobile teams. Walk through the work done in each area and identify the electrical equipment supporting it. Procurement and IT records can help, but may omit older equipment, borrowed items and appliances bought locally.
Give each area an owner who can confirm what is present and what has moved. This is particularly helpful for multi-shift or multi-building sites. A list maintained solely by the central facilities team may be neat while failing to reflect the equipment used outside normal office hours.
Use a simple walk-through route and mark each area when its inventory has been reviewed. Include equipment temporarily stored for later use, while distinguishing it from confirmed disposal stock. An area-based check helps reveal the gaps that purchasing records miss, such as shared kitchen items, spare power supplies and older tools that remain in service long after their original order has disappeared from view.
Use identifiers that survive a change of room
Assign a stable asset reference to the item rather than embedding its current room in its permanent identity. Record location in a separate field. Serial numbers can support identification, but may be hard to read or repeated on replacement parts. Make clear whether your organisation’s asset number and the contractor’s test reference are the same or linked.
For shared equipment, record the normal storage point and responsible team. Avoid personal data where project context is enough. A departmental custodian can remain useful through staff changes. The register should help someone locate an item or arrange its maintenance without needing to reconstruct who borrowed it months earlier.
Decide how components are represented
Include extension leads, detachable mains leads and power supplies in the planning discussion. A laptop, charger and detachable mains lead are a working set, but the contractor’s inspection and record method may represent the components separately. Ask how identifiers will show their relationship and how the quoted count is defined.
In a hypothetical training centre, a trolley contains laptops with interchangeable chargers. Labelling only the trolley can make later fault tracing difficult. Linking individual power supplies to a managed pool may be more useful than pretending each remains permanently paired with one computer. Choose a method that reflects actual use.
Record maintenance context, not just names
An item description alone does not explain exposure to damage. Include whether equipment is regularly moved, used outdoors, shared between teams or used in a demanding environment. Record manufacturer information where relevant and known problems reported by users. These fields support a risk-based plan rather than an automatic identical treatment for every object.
Keep technical classification and test selection with competent people. Staff preparing the register should not guess a safety class from the appearance of a plug. Mark uncertain details for confirmation. The inventory is a tool for maintenance planning, not evidence that equipment has passed an inspection simply because a row exists.
Reconcile exceptions after the visit
Compare the returned results with the expected inventory. Separate equipment assessed, not found, inaccessible, in use, failed, repaired and removed from service. Missing equipment should have an owner and follow-up action. An unused label or a copied previous result must not stand in for an assessment that did not happen.
Retain the previous history when an item changes location or status. That continuity makes repeated faults visible and lets the business judge whether the maintenance plan is working, rather than merely accumulating a fresh spreadsheet after every visit.
- Stable item identifier and a plain description are recorded.
- Current location and responsible team can be found without guesswork.
- Detachable leads, chargers and extensions have an agreed record method.
- Use conditions and reported defects reach the competent assessor.
- Absent items have a specific reason and recovery action.
- Additions, transfers, repairs and disposals update the live register.
PAT testing questions.
Is an inventory itself a legal PAT requirement?
HSE says portable-equipment maintenance logs and PAT labels are not generally required by the Electricity at Work Regulations. A useful inventory supports maintenance control, especially where equipment is numerous or mobile.
Should battery-powered devices be treated like mains appliances?
Distinguish the battery-powered device from its mains charger or supply. Tell the assessor what equipment is present so the relevant maintenance scope can be set without counting assumptions.
Portable equipment inspection programmes across business locations.
Multi-site PAT testing →Find the relevant service details, access considerations and information to include in an enquiry.
Find inspection advice for your industry →Find your site area →Prepare a site inspection list →Sources used for this guide.
The linked guidance supports the factual context. Check its jurisdiction and the requirements for your actual premises.
- HSE: Portable appliance testing questions ↗
Explains risk-based maintenance, new equipment, competence, and the position on annual testing, labels and records.
- HSE HSG107: Maintaining portable electrical equipment ↗
Supports equipment maintenance using user checks, formal visual inspections and appropriate tests, with decisions based on use, environment and findings.
- HSE INDG236: Maintaining portable equipment in low-risk environments ↗
Practical guidance for office-type equipment, visual checks and proportionate maintenance; its suggested starting intervals are not statutory deadlines.
PAT testing: scope & records.
See what the service includes and which site details help prepare a relevant quote.
View the service details